Alan M. Petrillo
National Fire Protection Association (NFPA) 1962, Standard for the Care, Use, Inspection, Service Testing and Replacement of Fire Hose, Couplings, Nozzles and Fire Hose Appliances (2013 ed.), makes a number of changes that affect how fire departments use some of the basic tools and equipment available to them in extinguishing fires.
The purpose of NFPA 1962, says Jim Glatts of FireOne and a member of the NFPA committee on fire hose that pulled together the revised standard, "is to provide a reasonable level of safety for users of fire hose and a reasonable degree of assurance that the hose, coupling assemblies, appliances, and nozzles will perform as designed."
Glatts points out that updating the standard was important when one considers the many changes in technology and materials that have been incorporated into hoselines, nozzles, appliances, and couplings over the years.
 |
(1) Fire departments now must system test together all of the elements that
go into a firefighting attack line. (Photos courtesy of FireOne.)
|
Change Rundown
The major changes made in the 2013 standard, Glatts says, include the following:
• Hose manufactured prior to July 1987 shall be removed from service.
• Nozzles shall be service tested at least as frequently as the hose to which it is attached.
• Attack fire hose shall be service tested to a minimum of 300 pounds per square inch (psi).
• Supply fire hose shall be service tested to a minimum of 200 psi.
• System tests shall be conducted at least annually on each preconnected line or any attack line used for interior firefighting operations on a fire apparatus, together with the nozzle or hose-connected appliance it supplies.
• All nonthreaded hose connections shall be provided with locks to ensure against unintentional disconnection.
• Fire hose users and the authority having jurisdiction (AHJ) shall establish a replacement schedule for their fire hose. The replacement schedule shall take into consideration the use, age, and testing results of the hose.
Jason Goodale, a company officer with Loveland (CO) Fire and Rescue Authority and NFPA Committee on Fire Hose member, says that although the revised standard covers a lot of ground, he doesn't think it will cause much difficulty in most fire departments. "There was some discussion before the standard was revised about having a shelf life for hose similar to that for personal protective equipment (PPE) of 10 years," Goodale says. "The committee found that it would be difficult for many fire departments to work under such a requirement for hose. It could be financially destructive to many of them having to replace a great deal of hose all at once."
 |
(2) Supply lines still must be tested annually to 200 psi, which is
unchanged from the previous NFPA 1962 edition.
|
Changing Materials
Glatts points out that hose materials and manufacturing standards have changed over the years, and those elements mean that hose is of higher quality and can take higher pressures. "The earlier version of the standard required attack hose to be tested to 250 psi and supply line to 200 psi," he says. "The new standard increases the pressure to 300 psi for attack line and leaves supply line the same. However, if a five-inch supply line becomes the sole source of an attack line