The purpose of the Fire Mechanics Section is to promote standardization of fire apparatus and equipment preventative maintenance, improve safety standards and practices, promote workshops, conferences, and seminars related to the purposes of this Section, and to promote cost savings through standardization of building and equipment purchasing and maintenance.

RECENT FIRE MECHANIC NEWS

Posted: Dec 8, 2013

I Have To Test What?

By Rod Carringer

Al Petrillo's great article on the impact of National Fire Protection Association (NFPA) 1962, Standard for the Care, Use, Inspection, Service Testing and Replacement of Fire Hose, Couplings, Nozzles and Fire Hose Appliances, (2013 ed.), in my perspective, alluded to what will be only the tip of the iceberg as it relates to the testing of nozzles and appliances. As we look more closely at the wording and intent of the standard, the ability of many departments to actually meet the requirements may actually be quite limited.

More than Hose

The expanded standard, aside from testing hose, requires the following:

• Handheld nozzles are all to be tested as frequently as the hose they are used on is tested and shall be both flow and hydrostatically tested.

• Hydrostatic testing requires a minimum of 300- up to 450-pound-per-square-inch (psi) pressures, and flow testing requires a calibrated flowmeter.

• All appliances such as gated wyes, manifolds, portable monitors, ball valves, and even intake valves are to be hydrostatically tested annually.

• Intake valves are to be removed from the apparatus and tested to the standard. The attached pressure relief valve shall be removed and tested separately.

• Suction hose is to be vacuum-tested and measured to 22 inches of mercury for 10 minutes, and a clear inspection cap is to be installed.

As the scope of these standard changes sinks in, I remain somewhat torn. On one hand, as I am a corporate officer of Task Force Tips (TFT), the focus on safety, service, and repair of noncompliant products, and even the recommended replacement schedule, is of the utmost importance to help keep our responders safe. On the other hand, as I am a nearly 40-year veteran of a small volunteer fire department, this is yet one more unfunded mandate we have to try to deal with. The burden of annual testing of hose, ladders, pumps, and now nozzles, appliances, and flow hardware forces us into a position of either committing scarce human and financial resources to accomplish the standard's compliance recommendations or accepting the potential liability should one of our untested and undocumented components fail during service.

As you can see, this really is a multifaceted issue and like it or not, since earlier this year, it's the law of the land when it comes to testing, inspection, care, and replacement of hose, nozzles, and appliances. If you are associated with a hose testing company or are a hose testing franchise owner, this standard and the associated business expansion are truly windfalls. But if you're an agency that has always maintained a "do-it-yourself" attitude when it comes to testing, maintenance, and service, there will certainly be some challenges to achieve compliance. As one of the world's largest producers of high-performance water flow equipment, TFT will continue to offer its perspective and interpretation of the performance and testing aspects of NFPA 1962. Following are some of the key areas of interest we've identified from conversations with distributors and emergency responders.

Hydrostatic Testing Equipment

When hydrostatically testing nozzles and appliances, the following criteria applies:

• Nozzles, appliances, and hardware shall be attached to a hydrostatic pressure source capable of exerting 300 psi, or 1.5 times the manufacturer's recommended maximum. For TFT, many items are rated at 300 psi, so the required equipment needs to exert up to 450-psi hydrostatic pressure, depending on the component being tested.

• The pressure being exerted on the product being tested shall be increased at each level by 50 psi and held for 30 seconds without visible leakage. At the maximum pressure, the hardware shall be held for 60 seconds with no visible leakage.

• Aside from the necessary calibrated gauge on the hydrostati

Read more
Posted: Dec 8, 2013

We've Suffered Enough

By Chris Mc Loone

I always enjoy putting together our December issue. Doing so gives me the chance to check in with industry suppliers and get an idea of where they feel their markets are headed in the coming year. Some might think, "Big deal. The tool manufacturers are optimistic. What's that got to do with me?" The answer is actually quite a bit.

When the manufacturers are saying that municipal budgets are showing less constraint, that means it's time for you to begin ensuring you get a piece of that pie. The Assistance to Firefighters Grant application period just opened, but it is time for us to stop relying on grant monies to accomplish what we need to do. If municipalities are starting to loosen the purse strings even a little bit, make sure you are the first in line to ensure your firefighters get new PPE, or that they get new apparatus that will stay out of the shop, or that they get SCBA that meets the most current edition of NFPA 1981.

You're not going to know whether or not your municipality has the money to spend unless you ask. The whole country knows we have suffered long enough, but what our budget directors are going to want is proof.

Data-Rich Environments

Like it or not, today we live in a world that is driven by data. We look at statistics to predict where the world economy is headed, whether to buy an ambulance or a pumper, or to plan our own capital improvements on our homes. Usually data are available at the click of a mouse. But, one area where many departments still struggle is documenting their activities to use as criteria for capital purchases.

For example, my department is working to achieve national accreditation. This has been a sometimes arduous process, especially in the beginning when we were getting systems in place to collect data regarding our training, our responses, our records, and attendance levels. Data collection required some companies in the department to change certain processes within their own organizations-no easy feat when most of the companies in the department are more than 100 years old and have been using their own processes the entire time.

Although the department is still several months away from finding out if it is accredited, the data we have collected have already resulted in many benefits. For one thing, we now have a more formal "seat at the table" with our elected commissioners. A few tangible benefits have been realized. We received funding for an expanded training program, which includes capital expenditures; we have expanded our training facility with a larger multipurpose training building; we constructed a training/storage building for the various training props and training equipment we have accrued; and, most importantly, at least one public safety training academy will send instructors to our facility for Firefighter I classes.

Another example is a preventive maintenance reimbursement program. The data we have collected have been used as justification for this program, under which each company is reimbursed by the township for preventive maintenance performed on apparatus, equipment, and facilities.

Obviously, not every department will realize such benefits. Economic realities are what they are. However, through a proactive program, it is possible to more effectively place your department "on the map" of your municipality, thus securing the funding necessary for you to continue providing the services your community has come to expect. Being able to prove you are doing what you say you are doing has benefits that transcend just counting pennies. It is hard to argue with data.

We have struggled enough during the economic downturn. The time is now for you to get your "seat at the table" and demand the funding that is long overdue for your department. If you have been assembling data, get them organized and present them effec

Read more
Posted: Dec 8, 2013

Technology Adoption, Cautious Optimism for 2014

Chris Mc Loone

If there's one thing the current economy has taught most of us, it's that there is no crystal ball we can use to predict when things are going to turn around. Even when things start to look like they're going pretty well, we again realize that very little of this is within our control. So, although things are pointing toward a 2014 that is better than 2013, the optimism remains understandably tempered.

Market Outlook

Many fire industry manufacturers are proceeding with caution considering the fragility of the economy. Things are better than they have been, but there is still a long way to go. "We are optimistic that municipal budgets will continue the improvement we have seen in the last couple of years," says Giff Swayne, president, Holmatro, Inc. "It is of course a fragile recovery, and there is still a good deal of pressure on fire department budgets. But, overall we are cautiously optimistic that the gains we have seen over the past couple of years will continue. During the depth of the recession and housing crisis, it was common to hear that departments were deferring purchases of new equipment because of budget cuts. But, we are not hearing that much anymore."

David Durstine, vice president, marketing, Akron Brass Company, says that his company is optimistic for the North American fire service and is looking forward to seeing industry growth in 2014. "Although we expect the growth to be mild, there is a pent-up demand as many fire departments have been delaying purchases or equipment upgrades over the past four to five years, and we are beginning to see a positive outlook on many city and state budgets."

Braun Industries is also looking forward to continued growth. "The economic indicators show a slight increase in growth for our industry in 2014," says Chad Brown, vice president, sales and marketing.

On the apparatus side, Bobby Williams, vice president, sales and marketing, Pierce Manufacturing, says federal demand will remain down, but the company continues to see evidence for improvement in municipal demand. "Some of the areas that were hit harder economically are now beginning to show signs of life," he says. "More of the larger fleet customers are starting the buying cycles, which is promising."

Economy's Effects

Of course, the general state of the economy will have an effect on the fire industry and municipality buying patterns. It's hard to pinpoint what the exact state of the economy is, but William Smith, president and CEO of Waterous, says, "Over the last two years, the economy has been stabilized and has been showing positive signs. As long as the government continues to support the fire service, 2014 will be a good year."

Keeping an eye on Washington, D.C., is key. "I wish that there was a defined state of the economy," says Swayne. "The gridlock in Washington, the uncertainty brought on by new legislations and regulations, and the roller coaster that is fiscal policy will play a role in our market in 2014. The problem is no one seems to have a clear understanding of where we are heading economically."

Durstine adds, "As we saw recently with the United States federal government shutdown, optimism could change at the flip of a coin or significant events beyond our control."

Braun cites the Affordable Care Act (ACA) as a potential influencer on companies in his market. "I think there is some hesitation in the marketplace with ACA and how that will impact the departments and agencies financially."

Swayne adds, "The recovery we have seen is fragile. Although the grants and Fire Administration funding seem to be intact for fiscal 2014, we need to keep a close eye on Washington and work with all industry stakeholders to ensure it stays that way."

Willi

Read more
Posted: Nov 12, 2013

Special Delivery: Busy Maryland Department Chooses PL Custom Ambulance for Three ALS Rigs

Alan M. Petrillo

The Bel Air (MD) Volunteer Fire Department (VFD) is one of the busiest volunteer departments in Maryland, covering an 80-square-mile area as first-due response and providing mutual aid to three counties. Last year Bel Air ran 6,495 emergency medical service (EMS) calls with four first-line advanced life support (ALS) ambulances.

Specific Need

Bel Air VFD, centrally located in Harford County, operates out of three stations and averages nearly 24 EMS calls a day, so quality, ease of maintenance, and reliability were chief concerns when the department looked to purchase a new ambulance, says Greg Sentman, the department's ambulance committee chairman. "PL Custom gave us the option of using a 12-volt hardwired electrical system instead of a multiplex system," Sentman says. "Because of the number of ambulance calls we run, the time required for service, as well as the ease of getting parts for a 12-volt system, we decided not to go with a multiplex system."

The Bel Air (MD) Volunteer Fire Department chose PL Custom Emergency Vehicles to build three Type 1 ambulances to upgrade its fleet

(1) The Bel Air (MD) Volunteer Fire Department chose PL Custom
Emergency Vehicles to build three Type 1 ambulances to upgrade its
fleet. (Photos courtesy of PL Custom Emergency Vehicles.)

 

Sentman notes, "It's easier to go to our local automotive electrical shop and buy a $10 relay rather than take an ambulance out of service to run it to a dealer's shop in Baltimore to adjust the multiplex." The onsite mechanic that PL Custom offered also was a selling point because his location was only about two hours away from Bel Air's main station.

Rig Trifecta

Shortly after Bel Air awarded the ambulance contract to PL Custom, the department increased its order to two identical ALS ambulances. Ultimately, Bel Air VFD ended up ordering a third rig from PL Custom, which is currently being built.

Chad Newsome, PL Custom's national sales manager, says that his firm had spoken with Bel Air in the past but that it was never able to get the department as a customer. "DPC Emergency Equipment, in Marydel, Maryland and Delaware, is the one that made this happen," Newsome says. "DPC was able to sell them the first ambulance, then Bel Air ordered a second, and now we are building a third for them. It's gratifying any time you are able to win a new account, but more so when they come back and order more trucks."

Bel Air opted to include a squad bench in its ambulances

(2) Bel Air opted to include a squad bench in its ambulances so their
interiors were similar to other ambulances in its fleet.

 

The ambulances are duplicate rigs, Newsome notes, with only small refinements among them and no wholesale changes. Each vehicle is built on a 2013 International 4300 M7 chassis and powered by a 300-hp International MaxxForce 7 diesel engine and an Allison 2200 EVS automatic transmission.

Jeff Hawkins, DPC Emergency Equipment's sales and marketing coordinator, says he brought a demo unit to Bel Air early in the purchasing process and after the specs were put out, PL Custom was one of three bidders for the contract. "It was a fairly clean bid spec where they wanted to duplicate their current interior layout but wanted the truck on a 12-volt electrical system," Hawkins says. "We were able to do that for the

Read more
RSS
First45974598459946004602460446054606Last

Theme picker

Upcoming Events

Theme picker

Sponsors

Fire Mechanics Section Board

Chair

Posted: Oct 21, 2015

Chair

Elliot Courage
North Whatcom Fire & Rescue
Read more

Vice Chair

Posted: Oct 21, 2015

Vice Chair

Mike Smith 
Pierce County Fire District #5
Read more

Secretary

Posted: Oct 21, 2015

Secretary

Greg Bach
South Snohomish County Fire & Rescue
Read more

Director #1

Posted: Oct 21, 2015

Director #1

Doug Jones
South Kitsap Fire & Rescue
Read more

Director #2

Posted: Oct 21, 2015

Director #2

Paul Spencer 
Fire Fleet Maintenance LLC
Read more

Director #3

Posted: Oct 21, 2015

Director #3

Jim Morris
Mountain View Fire Department
Read more

Director #4

Posted: Oct 21, 2015

Director #4

Arnie Kuchta

Clark County Fire District 6

Read more

Director #6

Posted: Oct 21, 2015

Director #6

Brett Annear
Kitsap County Fire District 18
Read more

Director #5

Posted: Oct 21, 2015

Director #5

Jay Jacks
Camano Island Fire & Rescue
Read more

Legislative Representative

Posted: Oct 21, 2015

Legislative Representative

TBD
TBD
Read more

Immediate Past Chair

Posted: Oct 20, 2015

Immediate Past Chair

Brian Fortner
Graham Fire & Rescue

Read more
RSS

Theme picker

2020 CAR SHOW